Below are trigger and macro settings for airport doors when using Mercury hardware and UnityIS.
Drive Gate Settings:
- Input Supervision for input 1: 0 normally closed
- Input Supervision for input 2: 1 normally open
- Note: If input 1 and/or input 2 are red, in the hardware properties, then check wiring
- Default reader mode: Card Only (for both readers)
- Door Held Time, Door Contact Input 2: 50 seconds
- Output 1 Pulse Time: 35 seconds
- Reader 1, Reader settings: 001-Paired (Master)
- Reader 2, Reader settings: 002-Paired (Slave)
Door Definitions:
- Door Strike: 0: door has no impact on strike control
- For Reader 1, select Paired (Slave) Reader: the second reader
- For Reader 2, select Paired (Master) Reader: the first reader
- Door Contact Address: Input 2
- REX1 Address: Input 3
- REX2 Address: None
Crash Bar Door Type:
- Door Strike Pulse Time = 5 seconds
- Door Held Open Time = 16 seconds
- Input #2 is a Monitor Point, no REX configuration
Baggage 30 Door Type:
- Door Strike Pulse Time = 10 seconds
- Door Held Open Time = 1800 seconds (30 minutes)
- Door Strike Mode = No Impact Only cards with Trigger Code 1 will work
Baggage 60 Door Type:
- Door Strike Pulse Time = 10 seconds
- Door Held Open Time = 3600 seconds (60 minutes)
- Door Strike Mode = No Impact Only cards with Trigger Code 1 will work
- Drive Gate Door Type: Door Strike Pulse Time = 45 seconds
- Door Held Open Time = 60 seconds
- Door Strike Mode = No Impact Only cards with Trigger Code 1 will work
- Input #2 is a Monitor Point, no REX configuration
Jetway Door Type:
- Door Strike Pulse Time = 5 seconds
- Output #2 Pulse Time = 5 seconds
- Door Held Open Time = 1800 seconds (30 minutes)
- Door Strike Mode = No Impact Only cards with Trigger Code 1 will work
- Input #2 is a Monitor Point, no REX configuration