Adding an RI2M Sub-Controller

The article below will guide you to add an RI2M sub-controller under an Azure IC2.

Prerequisites:

  • Follow the Hardware Manual for wiring the RI2M sub-controller to the IC2 controller
  • Ensure the hardware address is configured using the DIP switches on the RI2M. Each RI2M connected to the same IC2 must have a unique address.
  • Make sure to note the COM Port (either 1 or 2) of the IC2 controller to which the RI2M is connected.


Procedures:

  1. Login to the Web client with admin rights
  2. Go to Configuration>Hardware Manager
  3. In the hardware tree, select the IC2 controller where the RI2M is wired to
  4. Select the 'Address' dropdown button and select 'Add Sub-controller'
  5. In the Add Sub-Controller window, select 'RI2M Sub' under the Sub-Controller Type. In the Sub-Controller Address dropdown menu, select the address corresponding to the hardware address of the RI2M, 
  6. Click Add Sub-Controller button
  7. The RI2M sub-controller should now appear under the IC2 in the hardware tree
  8. Next, use Download Manager to send a 'Hardware' download for that IC2
  9. In the IC2 Controller Status screen, the RI2M should now show online